Introduction
JC100TE thermal resistance thermocouple input non-isolated temperature transmitter with the two-wire transmission method, the transmitter can be installed in the junction box of the thermocouple to form an integrated structure, or it can be separately installed in the instrument panel as a conversion unit.
For thermal resistance (RTD), thermocouple (TC) signal input, 2-wire 4-20mA output. Input and output are not isolated.
Use USB communication configuration; signal type, measurement range, alarm parameters, etc. can be programmed by PC software.
Input type
|
Item
|
Type
|
Measuring range
|
Min. Measuring range
|
Thermal resistance (RTD)
|
Pt100
|
-200~+850℃
|
10°C
|
Pt500,Pt1000
|
-200~+250℃
|
10°C
|
Cu50,Cu100
|
-50~+150℃
|
10°C
|
Ni100,Ni500
|
-60~+180℃
|
10°C
|
Ni1000
|
-60~+150℃
|
10°C
|
Thermocouple (TC)
|
B
|
0~+1820℃
|
500°C
|
E
|
-270~+1000℃
|
50°C
|
J
|
-210~+1200℃
|
50°C
|
K
|
-270~+1372℃
|
50°C
|
N
|
-270~+1300℃
|
50°C
|
R
|
-50~+1768℃
|
500°C
|
S
|
-50~+1768℃
|
500°C
|
T
|
-270~+400℃
|
50°C
|
Main technical parameters:
Input:
Input signal: Thermal resistance (RTD), Thermocouple (TC)
Thermal resistance Excitation current: 1mA
Thermocouple cold junction compensation: Compensation range: -25 °C ~ +75 °C(1 °C per 20 °C error)
Compensation method: internal compensation
Output :
Output Signal:4~20Ma(Loop power supply)
Output load resistance: RL ≤ 500Ω
Basic parameters:
Power: DC 12-36V
Accuracy: 0.1% F.S., 0.2% F.S.
Over-limit alarm: Below the lower temperature limit, output 3.8mA, (4-20mA output)
Above the upper temperature limit, output 20.5mA
Break alarm: output 22mA or 3.8mA
Temperature drift: 0.005% F.S./°C (-20°C~+55°C)
Response time: ≤1S (0-90%) (TYP)
Insulation strength: 1500V AC / 1min (between input, output, and power)
Insulation resistance: ≥100MΩ (between input, output, and power)
Operating temperature range: -20 ~ +55 ° C
Electromagnetic compatibility: Match GB/T 18268 (IEC61326-1)